Stationary batteries – fixed elements. In all buildings containing lead acid accumulators and battery rooms, there must be a sufficient amount of Neutrite S7 to completely extinguish the electrolyte contained in at least 2 elements composing the battery, for each battery installed. The amount of acid solution contained in the element must be attested by the manufacturer.
Stationary batteries – portable elements.
In all buildings used for storage, maintenance, recharging and, more generally, the movement of mobile stationary batteries (e.g. train lights) there must be a sufficient amount of Neutrite S7 to completely extinguish the electrolyte contained in the highest capacity battery for every 30 batteries provided in the system.
By way of example, the following table highlights the volume of acid solution that corresponds to the various capacities taken from the average of the values provided by the manufacturers of accumulators and the quantities of Neutrite S7 to have available.
|
|
|
|
|